Pictures may not be actual SKU

WCNP100 | W100P - Panel Mount Controllers - Conductivity - pH/OR - Disinfection

Product info
Description
Walchem's WCNP100 W100P Panel Mount Controllers for Conductivity - pH/ORP - Disinfection - 1/4 DIN Panel Mount
Configuration Model Codes
Base Model
Model
WCNP | Panel Mount - 1/4 DIN - Conductivity - pH/ORP - Disinfection
Power Option
Relays
110 | 4 dry
Availability Call to confirm
Select model  or  search within  this product range
Models are:  In Stock
Ships from PA - GA - FL - OH - TX
Typically ships within [ 0 to 2 ] days
24/7 Sales & Support 484-544-0506
Headline

W100P Series Controllers

The W100P series provide an economical and reliable way to keep your water treatment program under control.

Features & Benefits
Benefits:
  • Large display with icon based programming makes setup easy
  • Compact ¼ DIN panel mount enclosure
  • Universal sensor input provides extraordinary flexibility; the same controller can be used with almost any type of sensor needed; conductivity (contacting and electrodeless), amplified pH/ORP, or disinfection
  • Two pH/ORP/ISE models available for use with non-amplified electrodes with or without a BNC connector
  • Multiple language support allows simple setup no matter where your business takes you
  • Four control outputs allow the controller to be used in more places than other entry level models
  • Complete flexibility in the function of each relay
    • On/Off Setpoint
    • Time Proportional Control
    • Pulse Proportional Control (when purchased with solid-state rel ays)
    • In-range or Out-of-range activation
    • Timer-based activation
    • Activation based upon the state of a contact closure
    • Timed activation triggered by a Water Contactor or Paddlewheel flow meter’s accumulated total flow
    • Activate with another output
    • Alarm
Additional Notes
Specifications:
Inputs

Power 100-240 VAC, 50 or 60 Hz, 12 VA

Digital Input Signals (1) - State-Type Electrical: Optically-isolated input. Provides isolated 9V power. High-Speed Counter Current consumption when input is closed: 2.3 mA nominal. Typical response time: <2 seconds Devices supported: Any isolated dry contact (i.e. relay, reed switch) Types: Interlock

Low Speed Counter-Type Electrical: Optically-isolated input. Provides isolated 9V power. Current consumption when input is closed: 2.3 mA nominal. 0-10Hz, 50 msec minimum pulse width Devices supported: Any device with isolated open drain, open collector, transistor or reed switch Types: Contacting Flowmeter

High-Speed Counter-Type Electrical: Optically-isolated input. Provides isolated 9V power. Current consumption when input is closed: 2.3 mA nominal. 0-500Hz, 1.00 msec minimum pulse width Minimum pulse frequency for the rate to be displayed: 0.17 Hz Devices supported: Any device with isolated open drain, open collector, transistor or reed switch Types: Paddlewheel Flowmeter


Outputs

Dry contact mechanical relays (2 or 4 depending on model code 6 A (resistive), 1/8 HP (93W) per relay Dry contact relays are not fuse protected.

Pulse Outputs (0 or 2 model code dependent) Opto-isolated, solid-state relay, 200mA, 40V DC VLOWMAX = 0.05V @ 18mA Accuracy (0-10 Hz): ± 0.5% of Pulse Rate, (10-20 Hz): ± 1.0%, (20-40 Hz): ± 2.0%

4 - 20 mA (1) Internally powered, Fully isolated 600 Ohm max resistive load, Resolution 0.0015% of span Accuracy ± 0.5% of reading

Dimensional drawings
Call or text: +1 (484) 544-0506