Pictures may not be actual SKU

WCT900 | W900 - Cooling Tower - Conductivity Controller

Product info
Description
Walchem's WCT900 W900 Series Controllers for Cooling Towers - Conductivity
Configuration Model Codes
Base Model
Model
WCT | Cooling tower
Connections
Relays
900 | 8 powered
Availability Call to confirm
Select model  or  search within  this product range
Models are:  In Stock
Ships from PA - GA - FL - OH - TX
Typically ships within [ 0 to 2 ] days
24/7 Sales & Support 484-544-0506
Headline

W900 Series Water Treatment Controllers

Enjoy unparalleled versatility and powerful programming for complete control of chemical metering pumps and valves in a broad range of water treatment applications.

Features & Benefits
Features:
  • Powerful Control
  • WiFi, BACnet, Graph Reports
  • Flexible Programming
  • Online Access
  • Easy Setup
  • Great Value
Benefits:
  • Large touchscreen display with icon based programming makes setup easy

  • Universal sensor input provides extraordinary flexibility; the same controller can be used with almost any type of sensor needed

  • Four I/O slots allow complete flexibility in adding additional sensors, analog inputs and analog outputs

  • Multiple language support allows simple setup

  • Eight relay control outputs allow the controller to be used in more applications

  • Economical wall-mount package for easy installation

  • On-screen and web page graphing of sensor values and control output status

  • Complete function of each relay

    • On/Off Setpoint
    • Time Proportional Control
    • Pulse Proportional Control (when purchased with 4-20 mA or pulse solid state opto outputs)
    • Flow Proportional Control (when purchased with 4-20 mA or pulse solid state opto outputs)
    • PID control (when purchased with 4-20 mA or pulse solid state opto outputs)
    • In-Range or Out-of-Range activation
    • Probe wash
    • Timer-based activation
    • Activation based upon the state of a contact closure
    • Timed activation triggered by Water Contactor / Paddlewheel flow meter’s accumulated total flow
    • Activate with another output
    • Activate as a percent of another output’s on-time
    • Alarm
    • Spike Set Point
    • PPM Volume
    • Target PPM
    • For Cooling Tower and Boiler applications:
      • Biocide Timer
      • Boiler blowdown on conductivity using intermittent sampling
  • Ethernet for remote access via the Internet, LAN or optional Modbus/TCP

  • Datalogging

  • Email Alarm messages, Datalog reports or System Summary reports

Additional Notes
Specifications:
Inputs

Power 100-240 VAC, 50 or 60 Hz, 13A max Fuse: 6.3 Amp

Sensor Input Signals (0-8 depending on model code) Contacting Conductivity: 0.01, 0.1, 1.0, or 10.0 cell constant, or
Electrodeless Conductivity or Disinfection or Amplified pH, ORP, or Ion Selective Electrode which requires a preamplified signal. ±5VDC power available for external preamps. Walchem WEL or WDS series pH/ORP sensors recommended. Each sensor input card contains a temperature input. Temperature: 100 or 1000 ohm RTD, 10K or 100K Thermistor

Analog (4-20 mA) Sensor Input (0-24 depending on model code) 2-wire loop powered and self-powered transmitters supported 3-wire and 4-wire transmitters supported All Channels fully isolated, input and power Channel 1, 130 ohm input resistance, Channel 2-6, 280 ohm input resistance Available Power: Isolated 24 VDC ±15% supply per channel. 1.5 W (62.5 mA maximum for each channel)

Digital Input Signals (12): State-Type Digital Inputs Electrical: Optically isolated and providing an electrically isolated 12V power with a nominal 2.5 mA current when the digital input switch is closed. Typical response time: < 2 seconds. Devices supported: Any isolated dry contact (i.e. relay, reed switch). Types: DI State

Low Speed Counter-Type Digital Inputs Electrical: Optically isolated and providing an electrically isolated 12V power with a nominal 2.5 mA current when the digital input switch is closed, 0-20 Hz, 25 msec minimum width. Devices supported: Any device with isolated open drain, open collector, transistor or reed switch. Types: Contacting Flowmeter

High Speed Counter-Type Digital Inputs Electrical: Optically isolated and providing an electrically isolated 12V power with a nominal 2.5 mA current when the digital input switch is closed, 0-500 Hz, 1.0 msec minimum width. Devices supported: Any device with isolated open drain, open collector, transistor or reed switch. Types: Paddlewheel Flowmeter

Outputs

Powered Mechanical Relays (0-8 model code dependent) Pre-powered on circuit board switching line voltage Four relays are fused together as one group, total current must not exceed 6.3A (resistive), 1/8 HP (93W)

Dry Contact Mechanical Relays (0-8 model code dependent) 6 A (resistive), 1/8 HP (93W) Dry contact relays are not fuse protected.

Pulse Outputs (0-4 model code dependent) Opto-isolated, solid-state relay, 200mA, 40V DC VLOWMAX = 0.05V @ 18mA

4 - 20 mA (0-16 model code dependent) Internally powered, 15VDC, Fully isolated 600 ohm max resistive load Resolution 0.0015% of span Accuracy ± 0.5% of reading

Dimensional drawings
Alternate configurations
SKU Description List price -
WAL-WCT900HAABNDMNNNNNN WCT900H-AABN-DM-N-NNNNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Eth & WiFi - Modbus - No Sensors $4,620.00
WAL-WCT900HAABNDMPAFHNN WCT900H-AABN-DM-P-AFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Eth & WiFi - Modbus - Panel $6,274.00
WAL-WCT900HAABNDMPBFHNN WCT900H-AABN-DM-P-BFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Eth & WiFi - Modbus - Panel - 316 $6,274.00
WAL-WCT900HAABNDNNNNNNN WCT900H-AABN-DN-N-NNNNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Eth & WiFi - No Sensors $4,280.00
WAL-WCT900HAABNDNPAFHNN WCT900H-AABN-DN-P-AFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Eth & WiFi - Panel $5,934.00
WAL-WCT900HAABNDNPBFHNN WCT900H-AABN-DN-P-BFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Eth & WiFi - Panel - 316 $5,934.00
WAL-WCT900HAABNNMNNNNNN WCT900H-AABN-NM-N-NNNNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Modbus - No Sensors $4,393.00
WAL-WCT900HAABNNMPAFHNN WCT900H-AABN-NM-P-AFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Modbus - Panel $6,047.00
WAL-WCT900HAABNNMPBFHNN WCT900H-AABN-NM-P-BFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Modbus - Panel - 316 $6,047.00
WAL-WCT900HAABNNNNNNNNN WCT900H-AABN-NN-N-NNNNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - No Sensors $4,054.00
WAL-WCT900HAABNNNPAFHNN WCT900H-AABN-NN-P-AFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Panel $5,708.00
WAL-WCT900HAABNNNPBFHNN WCT900H-AABN-NN-P-BFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - Panel - 316 $5,708.00
WAL-WCT900HAABNWMNNNNNN WCT900H-AABN-WM-N-NNNNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - WiFi - Modbus - No Sensors $4,620.00
WAL-WCT900HAABNWMPAFHNN WCT900H-AABN-WM-P-AFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - WiFi - Modbus - Panel $6,274.00
WAL-WCT900HAABNWMPBFHNN WCT900H-AABN-WM-P-BFHNN | W900 Cooling Tower Controller - 8 Powered - HW - 2x Sensor - 2c 4-20mA - WiFi - Modbus - Panel - 316 $6,274.00
Call or text: +1 (484) 544-0506